BCM-0000-B Battery controller module

Commercial Type No.: BCM-0000-B
Product No.: F.01U.081.384

BCM-0000-B Battery controller module
  • Two voltage outputs of 2.8 A at 24 V each
  • Temperature-controlled charging and monitoring of batteries according to EN 54‑4:1997/A2:2006
  • Ready to go thanks to plug-and-play technology and pluggable terminal blocks
  • Overview
    Input voltage 20,4 V DC to 30 V DC
    Current consumption
    Standby 25 mA
    Fault 40 mA
    Voltage outputs
    2 outputs, switchable +24 V (20.4 - 30 V) 2,8 A battery-buffered (programmable)
    Capacity of the outputs BAT FAULT, AC FAULT and collective FAULT 0 V / 0 to 20 mA
    Maximum current of the module Max. 6 A
    to the panel rails (PRS 0002 A/PRD 0004 A) Max. 6 A
    of the outputs Max. 5.6 A (2 x 2.8 A, not in parallel wiring)
    Maximum battery resistance (fault threshold) 430 mΩ
    Permitted battery capacity
    with 2 batteries 24 – 26 Ah 36 – 45 Ah
    with 4 batteries 48 – 52 Ah 72 – 90 Ah
    Operating/display elements
    1 green LED Power ON
    3 yellow LEDs Trouble mains/batt. 1/batt. 2
    1 key Batteries charge at V < 21 V and central units start with battery current
    Housing material ABS plastic, Polylac PA-766 (UL94 V‑0)
    Housing color Satin finish, anthracite, RAL 7016
    Dimensions Approx. 127 x 96 x 60 mm(5.0 x 3.8 x 2.4 in.)
    Weight
    Without packaging Approx. 195 g (6.9 ounces)
    With packaging Approx. 340 g (12 ounces)
    Permitted operating temperature -5°C to 50°C (23°F to 122°F)
    Permitted storage temperature -20°C to 85°C (-13°F to 185°F)
    Permitted relative humidity 95%, non-condensing
    Protection class as per IEC 60529 IP 30